Richmond Permits & Inspections

Richmond, VA

Avg Review

24d

Rejection Rate

40%

Skill Files

8

Status

Medium

Ventilation — Richmond Type I Hood

VUSBC (2018 IMC w/ VA amendments) / NFPA 96
ventilation

Type I hoods per VUSBC mechanical. Same as Virginia Beach (statewide code). Exhaust 400 CFM/LF. Makeup air required.

Examiner Note: Richmond follows VUSBC. Same codes as Virginia Beach. Standard mechanical review.

Common rejection: Makeup air not shown; VA energy code not documented

Correction: Show makeup air on roof plan per VUSBC. Include VA energy code compliance.

Fire Suppression — Richmond NFPA 96

NFPA 96 / UL 300 / VA Statewide Fire Code
fire

UL 300 suppression. Richmond fire marshal reviews fire plans. Automatic gas shutoff.

Examiner Note: Richmond fire review as part of permit process.

Common rejection: UL 300 documents missing; fire plan incomplete

Correction: Include UL 300 documents. Show suppression on FP-1.

Plumbing — Richmond Grease Interceptor

VUSBC (2018 IPC w/ VA amendments) / Richmond DPU
plumbing

Grease interceptor per VUSBC plumbing. Richmond Department of Public Utilities reviews FOG. 3-comp sink.

Examiner Note: Richmond DPU reviews interceptor. Submit with permit.

Common rejection: Interceptor sizing missing; DPU review not initiated

Correction: Show interceptor sizing per VUSBC on P-1. Submit to Richmond DPU.

Electrical — Richmond Kitchen Circuits

2017 NEC w/ VA amendments / VUSBC
electrical

NEC with VA amendments per VUSBC. GFCI within 6 feet of water. Emergency disconnect. VA electrical license.

Examiner Note: Richmond follows VUSBC electrical. VA license required.

Common rejection: GFCI not shown; VA electrical license missing

Correction: Add GFCI on E-1. Include VA electrical license on application.

Health — Richmond Food Facility

12 VAC 5-421 / VDH Richmond
health

VDH reviews food facility plans per 12 VAC 5-421. Handwash, 3-comp sink, FRP, sealed floors. Same statewide requirements as Virginia Beach.

Examiner Note: VDH requires plan review. Standard VA food facility process.

Common rejection: VDH review not submitted; food facility layout incomplete

Correction: Submit food facility plan to VDH per 12 VAC 5-421.

Structural — Richmond Loads

VUSBC / ASCE 7-16
structural

Seismic Design Category B. Wind speed 115 mph. Equipment anchorage. VA PE required. Historic district considerations for older neighborhoods.

Examiner Note: Richmond has many historic districts. Verify if historic review applies. VA PE stamp required.

Common rejection: Historic district review not addressed; VA PE stamp missing

Correction: Provide VA PE-stamped calculations. Verify historic district applicability. Show equipment anchorage on S-1.

ADA — Richmond Accessible Design

VUSBC Ch. 11 / ADA 2010
ada

VUSBC accessibility. Standard ADA compliance. Accessible route, restroom.

Examiner Note: Richmond follows VUSBC accessibility. Standard review.

Common rejection: Accessible route not shown

Correction: Show accessible route on A-1 per VUSBC. Detail restroom.

Egress — Richmond Exit Requirements

VUSBC §1006 / §1017
egress

VUSBC egress. Two exits for 50+ occupants. Travel distance 250/300 feet.

Examiner Note: Richmond follows VUSBC egress.

Common rejection: Occupant load not on plans

Correction: Add occupant load per VUSBC on A-1. Show travel distance.