Long Beach Building & Safety Bureau

Long Beach, CA

Avg Review

30d

Rejection Rate

52%

Skill Files

8

Status

High Risk

Ventilation — Long Beach Type I Hood

2022 CMC 507 / NFPA 96 / LB Municipal Code
ventilation
42% rejection

Type I hoods per CMC 507. Title 24 energy compliance. Makeup air 80-100%. Long Beach has own building department separate from LADBS.

Examiner Note: Long Beach Building Bureau is separate from LA City. Verify LB-specific amendments. Title 24 compliance required.

Common rejection: Title 24 CF-1R missing; confusion between LADBS and LB Building Bureau requirements

Correction: Submit to Long Beach Building Bureau (not LADBS). Include CF-1R for kitchen HVAC. Show makeup air on roof plan.

Fire Suppression — Long Beach CFC/NFPA 96

2022 CFC / NFPA 96 / UL 300 / LBFD
fire

UL 300 suppression per CFC. Long Beach Fire Department (LBFD) reviews fire plans separately. Automatic gas shutoff. NFPA 13 sprinkler mods require LBFD review.

Examiner Note: LBFD requires separate fire plan review. Submit to LBFD concurrent with building permit.

Common rejection: Fire plans not submitted to LBFD; suppression documents incomplete

Correction: Submit fire plans to LBFD. Show UL 300 system, gas shutoff, and NFPA 13 modifications on FP-1.

Plumbing — Long Beach Grease Interceptor

2022 CPC / LB Water Dept
plumbing

Grease interceptor per CPC Table 10-4. Long Beach Water Department reviews FOG. 3-comp sink. Low-flow fixtures per CALGreen.

Examiner Note: LB Water has FOG program. Submit interceptor details to LB Water.

Common rejection: LB Water FOG review not initiated; interceptor sizing missing

Correction: Submit interceptor to LB Water FOG program. Show sizing per CPC Table 10-4 on P-1.

Electrical — Long Beach Kitchen Circuits

2022 CEC / Title 24
electrical

CEC requirements. GFCI within 6 feet of water. Emergency disconnect. Title 24 electrical compliance.

Examiner Note: LB follows CEC/Title 24. Standard CA electrical review.

Common rejection: GFCI missing; Title 24 electrical not documented

Correction: Add GFCI per CEC on E-1. Submit CF-1R electrical certificate.

Health — Long Beach Food Facility

CalCode §113700-114575 / LB Health Dept
health

Long Beach Health Department reviews food facility plans per CalCode. Long Beach is one of three CA cities with own health department (not county). Separate plan review.

Examiner Note: Long Beach Health Department (separate from LA County Health) requires own plan review application. 3-4 week turnaround.

Common rejection: Plan submitted to LA County Health instead of LB Health; food facility review not initiated

Correction: Submit food facility plan to Long Beach Health Department (not LA County Health). Show all fixtures and finishes per CalCode.

Structural — Long Beach Seismic Design

2022 CBC §1613 / ASCE 7-22
structural

Seismic Design Category D for Long Beach. Equipment anchorage critical. Walk-in cooler slab reinforcement. CA PE/SE required. Coastal zone considerations.

Examiner Note: LB requires CA PE/SE stamp. Standard CBC seismic review.

Common rejection: Seismic calculations incomplete; CA PE/SE stamp missing

Correction: Provide CA PE/SE-stamped seismic calculations per CBC 1613. Show equipment anchorage on S-1.

ADA — Long Beach Accessible Design

2022 CBC Ch. 11B / ADA 2010
ada

CBC 11B accessibility. CA standards exceed federal ADA. Path-of-travel for renovations.

Examiner Note: LB follows CBC 11B. Standard CA accessibility review.

Common rejection: CBC 11B requirements not met; path-of-travel analysis missing

Correction: Show accessible route per CBC 11B on A-1. Detail restroom per CBC 11B-604. Provide path-of-travel analysis.

Egress — Long Beach Exit Requirements

2022 CBC §1006 / §1017
egress

CBC egress. Two exits for 50+ occupants. Travel distance 250/300 feet. Exit signs on emergency power.

Examiner Note: LB follows standard CBC egress.

Common rejection: Occupant load missing; exit door widths not dimensioned

Correction: Add occupant load per CBC 1004 on A-1. Dimension exit doors.