Mesa Development Services

Mesa, AZ

Avg Review

18d

Rejection Rate

32%

Skill Files

8

Status

Medium

Ventilation — Mesa Type I Hood

2018 IMC 507 / NFPA 96
ventilation

Type I hoods per IMC. Same codes as Phoenix. Exhaust 400 CFM/LF. Makeup air 80-100%. Desert climate — extreme heat considerations for rooftop equipment.

Examiner Note: Mesa follows same codes as Phoenix. Fast electronic plan review. Show equipment temperature ratings.

Common rejection: Makeup air not shown; equipment not rated for desert heat

Correction: Show makeup air on roof plan rated for 115°F+ ambient. Include exhaust CFM calculations on M-1.

Fire Suppression — Mesa NFPA 96

NFPA 96 / UL 300 / Mesa Fire Code
fire

UL 300 suppression for Type I hoods. Mesa Fire reviews fire plans. Automatic gas shutoff. Manual pull station.

Examiner Note: Mesa Fire reviews as part of building permit. Streamlined process.

Common rejection: UL 300 documents missing; gas shutoff not shown

Correction: Include UL 300 documents. Show gas shutoff and nozzle layout on FP-1.

Plumbing — Mesa Grease Interceptor

2018 IPC / Mesa Utilities
plumbing

Grease interceptor per IPC. Mesa utilities may review FOG. 3-comp sink. Water conservation critical in desert. Low-flow fixtures required.

Examiner Note: Mesa follows standard IPC. Water conservation emphasized.

Common rejection: Interceptor sizing missing; water conservation fixtures not specified

Correction: Show interceptor sizing on P-1. Specify water conservation fixtures per Mesa code.

Electrical — Mesa Kitchen Circuits

2017 NEC
electrical

Dedicated circuits per appliance. GFCI within 6 feet of water. Emergency disconnect per NEC 422.33.

Examiner Note: Mesa follows standard NEC. Fast review.

Common rejection: GFCI not shown; emergency disconnect missing

Correction: Add GFCI within 6 feet of water on E-1. Show emergency disconnect.

Health — Mesa Food Facility

ARS §36-1761 / Maricopa County Environmental Health
health

Maricopa County Environmental Health reviews food facility plans. Handwash, 3-comp sink, FRP, sealed floors. Same as Phoenix requirements.

Examiner Note: Maricopa County EH serves both Phoenix and Mesa. Standard food facility review.

Common rejection: Health review not submitted; kitchen finishes incomplete

Correction: Submit food facility plan to Maricopa County Environmental Health. Specify finishes on A-series sheets.

Structural — Mesa Loads

2018 IBC §1607 / ASCE 7-16
structural

Seismic Design Category B for Mesa. Low seismic. No snow. Equipment anchorage. AZ PE required.

Examiner Note: Mesa follows standard IBC structural. AZ PE stamp required. Fast review.

Common rejection: AZ PE stamp missing

Correction: Provide AZ PE-stamped calculations. Show equipment anchorage on S-1.

ADA — Mesa Accessible Design

2018 IBC Ch. 11 / ADA 2010
ada

IBC Chapter 11 accessibility. Standard ADA compliance. Accessible route, restroom.

Examiner Note: Mesa follows standard IBC/ADA. Fast review.

Common rejection: Accessible route not dimensioned

Correction: Show accessible route on A-1. Detail restroom per IBC Ch. 11.

Egress — Mesa Exit Requirements

2018 IBC §1006 / §1017
egress

Standard IBC egress. Two exits for 50+ occupants. Travel distance 250/300 feet.

Examiner Note: Mesa follows standard IBC egress. Fast review.

Common rejection: Occupant load not on plans

Correction: Add occupant load per IBC 1004 on A-1. Show travel distance.