DC Department of Consumer & Regulatory Affairs (DCRA)

Washington, DC

Avg Review

38d

Rejection Rate

60%

Skill Files

8

Status

High Risk

Ventilation — DC Type I Hood

12A DCMR (DC Mechanical Code) / NFPA 96
ventilation
48% rejection

Type I hoods per DC Mechanical Code (12A DCMR based on IMC). Exhaust 400 CFM/LF heavy duty. Makeup air required. DC Green Building Act applies to commercial kitchens. DC energy code (12G DCMR) requirements.

Examiner Note: DCRA requires DC Green Building Act compliance for commercial projects. Include green building documentation with permit. LEED or Green Globes certification may be required.

Common rejection: DC Green Building Act compliance not documented; makeup air specifications incomplete

Correction: Include DC Green Building Act compliance documentation with permit. Show makeup air on M-1. Address 12G DCMR energy requirements for kitchen HVAC.

Fire Suppression — DC NFPA 96

NFPA 96 / UL 300 / 12F DCMR (DC Fire Code)
fire

UL 300 suppression for Type I hoods. DC Fire & EMS reviews fire plans separately from DCRA. Automatic gas shutoff. Manual pull station at egress. DC Fire requires separate permit.

Examiner Note: DC Fire & EMS requires separate fire suppression permit application. Submit to DC Fire before or concurrent with DCRA building permit.

Common rejection: Fire plans not submitted to DC Fire & EMS separately; suppression interlock with gas shutoff not shown

Correction: Submit fire suppression plans to DC Fire & EMS. Show UL 300 system, gas shutoff interlock, and pull station on FP-1.

Plumbing — DC Grease Interceptor

12B DCMR (DC Plumbing Code) / DC Water
plumbing

Grease interceptor per DC Plumbing Code (12B DCMR). DC Water reviews FOG compliance. 3-comp sink. Handwash within 25 feet. DC Water may require FOG control plan.

Examiner Note: DC Water FOG program has specific sizing requirements. Submit grease interceptor to DC Water for review.

Common rejection: DC Water FOG review not initiated; grease interceptor sizing not per 12B DCMR

Correction: Submit grease interceptor details to DC Water FOG program. Show sizing per 12B DCMR on P-1.

Electrical — DC Kitchen Circuits

12C DCMR (DC Electrical Code) / NEC w/ DC supplements
electrical

DC Electrical Code (12C DCMR based on NEC with DC supplements). GFCI within 6 feet of water. Emergency disconnect. DC-specific licensing requirements for electrical contractors.

Examiner Note: DCRA requires DC master electrician license for commercial work. Include license on application.

Common rejection: DC electrical contractor license not on application; GFCI requirements not met

Correction: Include DC master electrician license on application. Add GFCI within 6 feet of water on E-1. Show emergency disconnect.

Health — DC Food Facility

25 DCMR / DC Health (DOH)
health

DC Department of Health reviews food facility plans per 25 DCMR. Handwash, 3-comp sink, FRP behind cooking, sealed floors. DC Health requires Food Establishment License.

Examiner Note: DC Health requires separate food establishment plan review. Very thorough review — 4-6 week turnaround.

Common rejection: DC Health plan review not submitted; food facility specifications incomplete

Correction: Submit food facility plan to DC Health per 25 DCMR. Apply for Food Establishment License. Show all fixtures and finishes.

Structural — DC Loads

12A DCMR / 2017 IBC w/ DC supplements / ASCE 7-16
structural

Seismic Design Category B for DC. Equipment anchorage. Wind design. DC PE required for structural calculations. Historic buildings may have additional structural requirements.

Examiner Note: DCRA requires DC PE stamp. Historic district review may add structural restrictions for older buildings.

Common rejection: Structural calculations not by DC PE; historic district structural considerations not addressed

Correction: Provide DC PE-stamped calculations per 12A DCMR. Address historic district requirements if applicable.

ADA — DC Accessible Design

12A DCMR Ch. 11 / ADA 2010 / DC Human Rights Act
ada

DC supplements to IBC Chapter 11. Accessible route 36-inch clear. Accessible restroom. DC Human Rights Act provides additional protections. DC accessibility can exceed federal ADA.

Examiner Note: DCRA reviews accessibility carefully. DC has strong accessibility enforcement and may exceed federal ADA.

Common rejection: Accessible route not meeting DC accessibility supplements; restroom details incomplete

Correction: Show accessible route per 12A DCMR on A-1. Detail restroom per DC accessibility requirements. Address DC Human Rights Act compliance.

Egress — DC Exit Requirements

12A DCMR §1006 / §1017
egress

DC supplements to IBC egress. Two exits for 50+ occupants. Travel distance 250/300 feet. Exit signs on emergency power.

Examiner Note: DCRA follows DC supplements to IBC egress. Show occupant load on plans.

Common rejection: Occupant load not on plans; exit signs not on emergency power circuit

Correction: Add occupant load on A-1. Show exit signs on emergency power per 12A DCMR. Dimension travel distance.