Fort Worth Development Services Department

Fort Worth, TX

Avg Review

20d

Rejection Rate

35%

Skill Files

8

Status

Medium

Ventilation — Fort Worth Type I Hood

2021 IMC 507 / NFPA 96
ventilation

Type I hoods per IMC 507. Exhaust 400 CFM/LF heavy duty. Makeup air 80-100%. Similar to Dallas requirements. Hot climate — conditioned makeup air recommended.

Examiner Note: FW Dev Services follows same codes as Dallas. Show makeup air on roof plan with conditioned air specs.

Common rejection: Makeup air not shown; exhaust calculations missing

Correction: Show makeup air on roof plan per IMC 507. Include exhaust CFM calculations on M-1.

Fire Suppression — Fort Worth NFPA 96

NFPA 96 / UL 300 / FW Fire Code
fire

UL 300 suppression for Type I hoods. Fort Worth Fire Department reviews fire plans. Automatic gas shutoff. Manual pull station.

Examiner Note: FW fire review is consolidated with building permit. Include suppression details.

Common rejection: UL 300 manufacturer documents not included; gas shutoff not shown

Correction: Include UL 300 manufacturer documents. Show gas shutoff and nozzle layout on FP-1.

Plumbing — Fort Worth Grease Interceptor

2021 UPC / FW Water Dept
plumbing

Grease interceptor per UPC and Fort Worth Water Department. Interceptor sizing per UPC. 3-comp sink. FW Water may require FOG permit.

Examiner Note: FW Water Department reviews interceptor sizing. Submit with permit application.

Common rejection: Grease interceptor sizing missing; FW Water review not initiated

Correction: Show interceptor sizing per UPC on P-1. Submit to FW Water Department for FOG compliance review.

Electrical — Fort Worth Kitchen Circuits

2020 NEC / TX amendments
electrical

Dedicated circuits per appliance. GFCI within 6 feet of water. Emergency disconnect per NEC 422.33. Texas NEC amendments.

Examiner Note: FW follows Texas NEC amendments. Standard electrical review.

Common rejection: GFCI not shown near water sources; emergency disconnect missing

Correction: Add GFCI within 6 feet of water on E-1. Show emergency disconnect per NEC 422.33.

Health — Fort Worth Food Facility

TX Health & Safety Code §437 / Tarrant County Public Health
health

Tarrant County Public Health reviews food facility plans. Handwash, 3-comp sink, smooth surfaces, sealed floors. Separate health permit.

Examiner Note: Tarrant County Public Health requires separate application. 2-3 week turnaround.

Common rejection: Health department review not initiated; kitchen finishes incomplete

Correction: Submit food facility plan to Tarrant County Public Health. Specify finishes on A-series sheets.

Structural — Fort Worth Loads

2021 IBC §1607 / ASCE 7-16
structural

Seismic Design Category A/B. Low seismic. Wind speed 115 mph. Equipment anchorage. TX PE required.

Examiner Note: FW follows standard IBC structural. TX PE stamp required.

Common rejection: Structural calculations not by TX PE; equipment loads not addressed

Correction: Provide TX PE-stamped calculations. Show equipment anchorage on S-1.

ADA — Fort Worth TDLR & Accessible Design

TX Accessibility Standards (TAS) / TDLR / ADA 2010
ada

Texas Accessibility Standards via TDLR. TDLR project registration required. Accessible route 36-inch clear. Accessible restroom.

Examiner Note: FW requires TDLR registration number on permit. Complete before submitting.

Common rejection: TDLR registration not completed; accessible route missing

Correction: Complete TDLR registration. Show accessible route and restroom per TAS on A-1.

Egress — Fort Worth Exit Requirements

2021 IBC §1006 / §1017
egress

Standard IBC egress. Two exits for 50+ occupants. Travel distance 250/300 feet. Exit signs on emergency power.

Examiner Note: FW follows standard IBC egress.

Common rejection: Occupant load not on plans; exit signs not on emergency circuit

Correction: Add occupant load per IBC 1004 on A-1. Show exit signs on emergency power.