City of Jacksonville Building Inspection Division

Jacksonville, FL

Avg Review

25d

Rejection Rate

45%

Skill Files

8

Status

Medium

Ventilation — Jacksonville Type I Hood

2020 FBC Mechanical / NFPA 96
ventilation

Type I hoods per FBC Mechanical. Exhaust 400 CFM/LF heavy duty. Makeup air 80-100%. Florida climate: dehumidification of makeup air critical. Hurricane-rated roof penetrations for exhaust fans.

Examiner Note: Jacksonville requires hurricane-rated curb details for rooftop exhaust fans. Show Miami-Dade product approval or Florida Product Approval for roof-mounted equipment.

Common rejection: Rooftop equipment not showing Florida Product Approval; makeup air dehumidification not addressed

Correction: Show Florida Product Approval numbers for rooftop exhaust equipment. Include dehumidification specifications for makeup air. Show hurricane-rated curb details on roof plan.

Fire Suppression — Jacksonville NFPA 96

NFPA 96 / UL 300 / FBC Fire Prevention
fire

UL 300 suppression for Type I hoods. Jacksonville Fire & Rescue reviews fire plans. Automatic gas shutoff. Manual pull station. FBC fire prevention code applies.

Examiner Note: Jacksonville Fire Marshal reviews as part of permit. Include fire suppression in building permit submittal.

Common rejection: UL 300 manufacturer documents missing; fire suppression plan not detailed

Correction: Include UL 300 manufacturer documents. Show nozzle layout, gas shutoff, and pull station on FP-1 per FBC and NFPA 96.

Plumbing — Jacksonville Grease Interceptor

2020 FBC Plumbing / JEA Pretreatment
plumbing

Grease interceptor per FBC Plumbing and JEA (Jacksonville Electric Authority) pretreatment requirements. JEA reviews interceptor sizing. 3-comp sink. Handwash within 25 feet.

Examiner Note: JEA reviews grease interceptor separately from building permit. Submit to JEA early.

Common rejection: JEA pretreatment review not initiated; interceptor sizing not meeting JEA requirements

Correction: Submit grease interceptor to JEA pretreatment. Show sizing per FBC Plumbing on P-1. Include fixture count and flow rates.

Electrical — Jacksonville Kitchen Circuits

2020 NEC / FBC Electrical
electrical

Dedicated circuits per appliance per FBC Electrical. GFCI within 6 feet of water. Emergency disconnect per NEC 422.33. Florida follows NEC closely.

Examiner Note: Jacksonville follows FBC Electrical. Standard NEC compliance.

Common rejection: GFCI not shown on kitchen circuits; emergency disconnect missing

Correction: Add GFCI symbols within 6 feet of water on E-1. Show emergency disconnect per NEC 422.33.

Health — Jacksonville Food Facility

FL Statutes §509 / FL DBPR / Duval County Health
health

Florida DBPR (Dept of Business & Professional Regulation) licenses food service. Duval County Health Department reviews food facility plans. Handwash, 3-comp sink, FRP behind cooking, sealed floors.

Examiner Note: Duval County Health requires plan review. DBPR food service license needed before operations. Apply for both early.

Common rejection: Health department plan review not submitted; DBPR license not applied for

Correction: Submit food facility plan to Duval County Health. Apply for DBPR food service license. Show all required fixtures on floor plan.

Structural — Jacksonville Wind Design

2020 FBC §1609 / ASCE 7-16
structural

Seismic Design Category A for Jacksonville. Wind design critical — basic wind speed 130-140 mph (Exposure C). Hurricane-rated building envelope. Equipment anchorage for wind and seismic. FL PE required.

Examiner Note: Jacksonville enforces FBC wind design strictly. All roof-mounted equipment must have wind resistance documentation.

Common rejection: Wind load calculations incomplete; roof equipment wind resistance not documented

Correction: Provide FL PE-stamped structural calculations with wind loads per FBC §1609. Document wind resistance for all roof equipment.

ADA — Jacksonville Accessible Design

2020 FBC Accessibility / ADA 2010
ada

FBC Accessibility provisions. Accessible route 36-inch clear. Accessible restroom. Florida Accessibility Code may differ from federal ADA in some areas. Vertical accessibility required in multi-story.

Examiner Note: Jacksonville follows FBC Accessibility. Standard compliance expected.

Common rejection: Accessible route not shown; FBC Accessibility restroom requirements not met

Correction: Show accessible route on A-1 per FBC Accessibility. Detail restroom with 60-inch turning circle.

Egress — Jacksonville Exit Requirements

2020 FBC §1006 / §1017
egress

FBC egress. Two exits for 50+ occupants. Travel distance 250/300 feet. Exit signs on emergency power. Panic hardware for 50+ occupants.

Examiner Note: Jacksonville follows FBC egress. Ensure occupant load is on plans.

Common rejection: Occupant load not on plans; exit signs not on emergency power

Correction: Add occupant load per FBC 1004 on A-1. Show exit signs on emergency power. Dimension travel distance.