Charlotte-Mecklenburg Code Enforcement

Charlotte, NC

Avg Review

24d

Rejection Rate

40%

Skill Files

8

Status

Medium

Ventilation — Charlotte Type I Hood

2018 NC Mechanical Code / NFPA 96
ventilation

Type I hoods per NC Mechanical Code (based on IMC with NC amendments). Exhaust 400 CFM/LF heavy duty. Makeup air required. NC Energy Code applies to kitchen exhaust systems.

Examiner Note: Charlotte-Mecklenburg follows NC Building Code. Show energy code compliance for kitchen HVAC on M-sheets.

Common rejection: Makeup air not shown; NC energy code compliance not documented for kitchen HVAC

Correction: Show makeup air unit on M-1/roof plan. Include NC energy code compliance documentation for kitchen HVAC systems.

Fire Suppression — Charlotte NFPA 96

NFPA 96 / UL 300 / NC Fire Code
fire

UL 300 suppression for Type I hoods. Charlotte Fire Department reviews fire plans. Automatic gas shutoff. Manual pull station at egress. K-class extinguisher within 30 feet.

Examiner Note: Charlotte Fire reviews as part of consolidated review process. No separate fire application required.

Common rejection: UL 300 manufacturer documents not included with plans; gas shutoff not detailed

Correction: Include UL 300 system manufacturer documents with permit application. Show gas shutoff valve and manual pull station on FP-1.

Plumbing — Charlotte Grease Interceptor

2018 NC Plumbing Code / Charlotte-Mecklenburg Utilities (CMU)
plumbing

Grease interceptor per NC Plumbing Code and CMU requirements. Interceptor sizing per fixture count. 3-comp sink required. CMU may require separate FOG compliance review.

Examiner Note: CMU reviews grease interceptor as part of utility connection permit. Submit grease interceptor details to CMU.

Common rejection: Grease interceptor not reviewed by Charlotte-Mecklenburg Utilities; sizing calculations missing

Correction: Submit grease interceptor sizing to CMU. Show interceptor details on P-1 with fixture count and flow rate calculations.

Electrical — Charlotte Kitchen Circuits

2017 NEC w/ NC amendments
electrical

Dedicated circuits per appliance. GFCI within 6 feet of water. Emergency disconnect per NEC 422.33. NC amendments to NEC apply.

Examiner Note: Charlotte follows NC amendments to NEC. Standard review process.

Common rejection: GFCI protection not shown on kitchen circuits near water sources

Correction: Add GFCI symbols within 6 feet of water on E-1. Show emergency disconnect location per NEC 422.33.

Health — Charlotte Food Facility

NC GS §130A / Mecklenburg County Health Dept
health

Mecklenburg County Health Department reviews food facility plans per NC General Statutes. Handwash, 3-comp sink, smooth surfaces, FRP behind cooking, sealed floors. Separate application required.

Examiner Note: Mecklenburg County Health requires plan review before building permit issuance. Apply concurrently with building permit.

Common rejection: Health dept plan review not submitted; food prep surface specifications incomplete

Correction: Submit food facility plan review to Mecklenburg County Health. Specify all food contact and wall surfaces on A-series sheets.

Structural — Charlotte Wind & Seismic

2018 NC Building Code / ASCE 7-16
structural

Seismic Design Category B for Charlotte. Wind speed 115 mph per ASCE 7. Equipment anchorage for items over 400 lbs. Standard floor loading per NC Building Code. NC-licensed PE required.

Examiner Note: Charlotte follows NC Building Code structural provisions. NC PE stamp required on structural calculations.

Common rejection: Structural calculations not stamped by NC PE; wind load calculations incomplete

Correction: Provide NC PE-stamped structural calculations. Include wind and seismic load analysis per ASCE 7. Show equipment anchorage on S-1.

ADA — Charlotte Accessible Design

2018 NC Building Code Ch. 11 / ADA 2010
ada

NC Building Code accessibility provisions based on IBC Chapter 11. Accessible route 36-inch clear. Accessible restroom. NC follows federal ADA closely with some additional state requirements.

Examiner Note: Charlotte reviews accessibility per NC Building Code. Standard ADA compliance expected.

Common rejection: Accessible route not dimensioned on floor plan; restroom accessibility details incomplete

Correction: Show accessible route on A-1 with dimensions. Detail restroom per NC Building Code Ch. 11 with 60-inch turning circle and grab bars.

Egress — Charlotte Exit Requirements

2018 NC Building Code §1006 / §1017
egress

NC Building Code egress requirements. Two exits for 50+ occupants. Travel distance 250/300 feet. Exit signs on emergency power. Panic hardware for 50+ occupants.

Examiner Note: Charlotte follows standard NC Building Code egress. Ensure occupant load calculation is visible on plans.

Common rejection: Occupant load not calculated on plans; exit sign power source not identified

Correction: Add occupant load calculation on A-1. Show exit signs connected to emergency power on E-1/RCP.