Metro Nashville Dept of Codes & Building Safety

Nashville, TN

Avg Review

22d

Rejection Rate

38%

Skill Files

8

Status

Medium

Ventilation — Nashville Type I Hood

2018 IBC / IMC 507 w/ TN amendments / NFPA 96
ventilation

Type I hoods required over grease-producing appliances per IMC. Exhaust 400 CFM/LF heavy duty. Makeup air at 80-100% of exhaust. TN amendments follow standard IMC. Hot/humid climate requires dehumidification considerations for makeup air.

Examiner Note: Metro Nashville follows standard IMC. Makeup air dehumidification recommended but not always enforced. Show makeup air on roof plan.

Common rejection: Makeup air unit not shown on roof plan; exhaust CFM calculation not provided

Correction: Show makeup air unit on roof plan with CFM matching exhaust per IMC 507. Include exhaust rate calculations on M-1. Consider dehumidification for Nashville climate.

Fire Suppression — Nashville NFPA 96

NFPA 96 / UL 300 / Nashville Fire Code
fire

UL 300 suppression for all Type I hoods. Nashville Fire Marshal reviews fire plans separately. Automatic gas shutoff. Manual pull station at egress. K-class extinguisher within 30 feet of cooking.

Examiner Note: Nashville Fire Marshal requires separate fire review application. Submit concurrent with Metro building permit.

Common rejection: Fire suppression plans not submitted to Nashville Fire Marshal separately

Correction: Submit fire suppression plans to Nashville Fire Marshal. Show UL 300 nozzle layout, gas shutoff, and manual pull station on FP-1. Locate K-class extinguisher within 30 feet.

Plumbing — Nashville Grease Management

2018 IPC w/ TN amendments / Metro Water Services
plumbing

Grease interceptor per IPC and Metro Nashville Water Services (MWS) requirements. Interceptor sizing per IPC. 3-comp sink. Handwash within 25 feet. MWS may require FOG (fats, oils, grease) permit.

Examiner Note: MWS reviews grease interceptor sizing. Submit grease trap/interceptor details to MWS in addition to Metro building permit.

Common rejection: Grease interceptor not reviewed by Metro Water Services; FOG permit not applied for

Correction: Submit grease interceptor details to Metro Water Services. Show sizing calculations on P-1. Apply for FOG permit if required by MWS.

Electrical — Nashville Kitchen Circuits

2017 NEC / TN amendments
electrical

Dedicated circuits per appliance. GFCI within 6 feet of water per NEC 210.8(B). Emergency disconnect per NEC 422.33. Tennessee follows standard NEC with minimal amendments.

Examiner Note: Metro Nashville follows standard NEC. No unusual local requirements.

Common rejection: GFCI protection not shown on kitchen circuits; emergency disconnect location missing

Correction: Add GFCI symbols within 6 feet of water on E-1. Show emergency disconnect location per NEC 422.33.

Health — Nashville Food Facility

TN Code §68-14 / Metro Nashville Health Dept
health

Metro Nashville Health Department reviews food facility plans. Handwash sink, 3-comp sink, smooth surfaces, FRP behind cooking, sealed floors. Separate permit from building permit. Must obtain Health Dept approval before occupancy.

Examiner Note: Metro Health requires separate plan review application. Submit early — 3-4 week turnaround.

Common rejection: Health department plan review not initiated; wall finish behind cooking line not specified

Correction: Submit food facility plan to Metro Nashville Health Department. Specify FRP/stainless behind cooking on A-series. Show handwash sink locations.

Structural — Nashville Loads

2018 IBC §1607 / ASCE 7-16 w/ TN amendments
structural

Seismic Design Category B/C for Nashville. Equipment anchorage for items over 400 lbs. Floor live load 150 PSF for commercial kitchen. Walk-in cooler slab reinforcement. Wind design per ASCE 7 (90-100 mph basic wind speed).

Examiner Note: Metro Nashville follows standard IBC structural. TN-licensed PE required for structural calculations.

Common rejection: Structural calculations not provided by TN PE; equipment anchorage details missing

Correction: Provide TN PE-stamped structural calculations. Add equipment anchorage on S-1. Show walk-in cooler slab design.

ADA — Nashville Accessible Design

2018 IBC Ch. 11 w/ TN amendments / ADA 2010
ada

IBC Chapter 11 accessibility with TN amendments. Accessible route 36-inch clear. Accessible restroom 60-inch turning radius. Tennessee follows federal ADA closely.

Examiner Note: Metro Nashville follows standard IBC/ADA accessibility. No significant local deviations.

Common rejection: Accessible restroom dimensions not meeting IBC Ch. 11; accessible route not dimensioned

Correction: Show accessible route on A-1 with dimensions per IBC Ch. 11. Detail restroom with 60-inch turning circle and grab bars.

Egress — Nashville Exit Requirements

2018 IBC §1006 / §1017 w/ TN amendments
egress

Standard IBC egress. Two exits for 50+ occupants. Travel distance 250/300 feet. Exit signs on emergency power. Panic hardware for 50+ occupants. Occupant load on plans.

Examiner Note: Metro Nashville follows standard IBC egress requirements.

Common rejection: Occupant load not on plans; travel distance not shown

Correction: Add occupant load per IBC 1004 on A-1. Show travel distance on egress plan. Dimension exit door widths.